Screen |
3.5” TFT-LCD 및 터치 패널을 통한 인터페이스 |
Pattern |
Max 100 , Available to operate each channel's pattern |
Segment |
Max 2,400 ( Max 100 per segment) |
Waiting Mode |
Setup per pattern and setup of using or not using per segment |
Repetition & Connection |
Available to use Pattern Repetition and Section Repeat Loof Setup (Max. 20) Free connecting operation among patterns is available |
PID Group |
Each channel 4 Zones, Selectable between manual or automatic |
Control Method |
Heating control or Heating/Cooling control in each channel. PID or ON/OFF control |
Auto Tuning |
Optimal PID GAIN is automatically calculated according to Set Value.
It could be operated by each channel |
Proportional Band |
0.0 ~ 1000.0 ℃ ( If "0" = On/Off control, Not "0" = PID control) |
Integral Time |
0 ~ 6000 sec ( "0" = No Integral Calculation) |
Differential Time |
0 ~ 6000 sec ( "0" = No Differential Calculation) |
ON/OFF control |
Available to select Dead zone 0.1 ~ 1000.0 ℃ |
Event Log |
Max 40 Event Logs could be saved depend on various situations |
LCD protection |
Back light will be off according to designated time of not using touch panel |
Password |
Password is available to prevent other people from changing system setup |
Protection of Over-Integral and Differential |
ARW Zone setup ( 50 ~ 200 % of proportional band) |
Fuzzy Function |
Control overshoot |
RAMP |
Available to select SV changing ratio in case of fixing operation |
Restrict MV
changing ratio |
Function to control sudden change of MV |
Alarm Setup |
4 points, High, Low, Deviation etc. 20 kinds |
Inner Signal |
8 points, object, range and delayed time setup are available |
Time Signal |
8 points when program mode operation |
Graph Function |
PV, SV of each channel could be display by graph |
Fixing Operation Hour |
Available to set fixing operation hour up |
Reservation
Operation Fuction |
Available to use reservation operation time by using built in timer. |
User Logo Display |
User logo could be shown for 3 sec after power on. Download through communication port |
Screen Capture |
Upload is available through communication port |
Language |
Korean and English (Or Chinese / English optional) |
Contact Input |
RUN/STOP, STEP, HOLD and Error Input
(Stop operation, Delayed/ setup is available) |
Contact Output |
Output of various signals |
Storage in Power Failure |
Various setting and operation information memory |
정전복귀 |
STOP / COLD / HOT return when power failure is restored |